|
|
Brian Sims
Editor |
| Home> | Fire | >Suppression | >Sprinklers contain third floor flat fire in high-rise residential block |
Sprinklers contain third floor flat fire in high-rise residential block
13 February 2026
AS REPORTED by the British Automatic Fire Sprinkler Association (BAFSA), a recent fire that began in the kitchen of an open-plan kitchen/lounge flat on the third floor of a 17-storey residential block in London was successfully contained by the building’s sprinkler system, preventing what could have been a far more serious incident.

The fire is believed to have started accidentally when cooking oil ignited in a pan. One occupant safely left the building before the arrival of firefighters from the London Fire Brigade.
Crucially, two concealed sprinkler heads activated in response to the rising heat at ceiling level. As temperatures increased, the cover plate of the sprinkler nearest the fire disengaged, in turn releasing the deflector plate.
Continued heat exposure caused the liquid within the sprinkler’s glass bulb to expand until it shattered, releasing the plug and allowing water to discharge. The water struck the deflector, creating a uniform spray pattern directly over the fire. This rapid and automatic response controlled and contained the fire at its earliest stages.
Evidence of effectiveness
Evidence of the sprinkler system’s effectiveness was clear. The cooking extractor fan positioned directly above the seat of the fire was completely destroyed, while smoke staining was visible at ceiling level and on nearby wall units. However, a distinctive circular water spray pattern around the activated sprinkler head showed where the water had prevented smoke jets from spreading further across the ceiling.
Fire damage was limited to the immediate area, significantly reducing the potential for fire spread throughout the flat or beyond. Once firefighters confirmed the fire was fully extinguished, the sprinkler system serving the individual flat was isolated.
The sprinkler system had been installed in accordance with BS 9251 – the Code of Practice for Fire Sprinkler Systems in Domestic and Residential Occupancies – and was supplied by a shared cold-water booster main.
Operational evidence
According to BAFSA, this incident provides “powerful operational evidence” of the life-saving and property-protecting benefits of residential sprinklers. In a 17-storey building, an uncontrolled kitchen fire could have developed on a rapid basis, threatening multiple floors and placing residents and firefighters at significant risk. Instead, the sprinkler system intervened automatically, duly containing the fire before it could escalate.
The Government’s 2020 decision to lower the height threshold for mandatory sprinklers in new residential blocks from 30 metres to 11 metres was an important step forward. However, many existing residential buildings remain without this vital form of protection.
*Further information is available online at www.bafsa.org.uk
- Business Sprinkler Alliance supports sustainability agenda at CABE 2022
- MEPs support inclusion of fire resilience within EU Green Deal initiatives on buildings
- European cladding standard eliminates “misleading” fire tests
- Brandon Lewis named Security Minister
- Fundraising challenge launched in bid to support fire service key workers
- London Borough of Lewisham fails to meet consumer standards on fire safety
- Eight breaches of Fire Safety Order in County Durham lead to prosecution
- Firefighters mark 30th anniversary of King’s Cross fire
- Latest release of Synergy software platform unveiled by Synectics
- Security Industry Authority appoints new CEO









